Vaporproof Lighting

» Class I and II Definitions
UL Standards and Codes

CLASS I

Flammable Gases, Vapors or Liquids

CLASS II

Combustible Dusts

CLASS I AREA CLASSIFICATION

CLASS II AREA CLASSIFICATION

Division 1:

Where ignitable concentrations of flammable gases, vapors or liquids can exist all of the time or some of the time under normal operating conditions.

Zone 0:

Where ignitable concentrations of flammable gases, vapors or liquids are present continuously or for long periods of time under normal operating conditions.

Zone 1:

Where ignitable concentrations of flammable gases, vapors or liquids are likely to exist under normal operating conditions.

Division 1:

Where ignitable concentrations of combustible dusts can exist all of the time or some of the item under normal operating conditions.

Division 2:

Where ignitable concentrations of flammable gases, vapors or liquids are not likely to exist under normal operating conditions.

Zone 2:

Where ignitable concentrations of flammable gases, vapors or liquids are not likely to exist under normal operating conditions.

Division 2:

Where ignitable concentrations of combustible dusts are not likely to exist under normal operating conditions.

CLASS I GROUPS

CLASS II GROUPS

Division 1 and 2

Zone 0, 1 and 2

Division 1 and 2

A (acetylene)

IIC (acetylene & hydrogen)

E (metals - Div. 1 only)

B (hydrogen)

IIB (ethylene)

F (coal)

C (ethylene)

IIA (propane)

G (grain)

D (propane)

 

 

CLASS I TEMPERATURE CODES

CLASS II TEMPERATURE CODES

Division 1 and 2

Zone 0, 1 & 2

Division 1 and 2

T1 (≤450°C)

T1 (≤450°C)

T1 (≤450°C)

T2 (≤300°C)

T2 (≤300°C)

T2 (≤300°C)

T2A, T2B, T2C, T2D

(≤280°C, ≤286°C, ≤230°C, ≤215°C)

------------

T2A, T2B, T2C, T2D

(≤280°C, ≤286°C, ≤230°C, ≤215°C)

T3 (≤200°C)

T3 (≤200°C)

T3 (≤200°C)

T3A, T3B, T3C (≤180°C, ≤165°C, ≤160°C)

------------

T3A, T3B, T3C (≤180°C, ≤165°C, ≤160°C)

T4 (≤135°C)

T4 (≤135°C)

T4 (≤135°C)

T4A (≤120°C)

------------

T4A (≤120°C)

T5 (≤100°C)

T5 (≤100°C)

T5 (≤100°C)

T6 (≤85°C)

T6 (≤85°C)

T6 (≤85°C)

CLASS I, DIVISION 1 AND 2 PROTECTION METHODS

CLASS II, DIVISION 1 AND 2 PROTECTION METHODS

Application Certification Documents

Application Certification Documents
Area / Protection Methods
USA
Canada
Area / Protection Methods
USA
Canada
Div.1
Explosion proof
Intrinsically safe (2 Fault)
Purged/pressurized (Type X or Y)

ANSI/UL 1203
ANSI/UL 913
ANSI/NFPA 496

CSA-30
CSA-157
ANSI/NFPA 496

Div.1
Dust-ignition proof
Intrinsic safe
Pressurized

ANSI/UL 1203
ANSI/UL 913
ANSI/NFPA 496

CSA-25 or CSA-E61241-1-1
CSA-157
ANSI/NFPA 496

Div. 2
Hermetically sealed
Nonincendive
Non-sparking
Purged/pressurized (Type Z)
Any Class 1, Div. 1 method
Any Class 1, Zone 0, 1 or 2 method


UL 1604
UL 1604
UL 1604
ANSI/NFPA 496
-------
UL 60079 series


CSA-213
CSA-213
CSA-213
ANSI/NFPA 496
-------
CSA E60079 series
Div. 2
Dust tight
Hermetically sealed
Nonincendive
Pressurized
Any Class II, Div. 1 method
UL 1604
UL 1604
UL 1604
NFPA 496
-------
CSA-157 or CSA-E61241-1-1
-------
-------
NFPA 496
-------